9.3.2. Directional current protection
Directional overcurrent stages I
dir
> and I
dir
>> (67)
Directional/non-directional
Minimum voltage for the direction solving
0.06
**)
– 300.00 s (step 0.02 s)
EI, VI, NI, LTI, MI…depends on the family *)
0.50 – 20.0 for RXIDG, IEEE and IEEE2
Transient over-reach, any τ
- Starting (rated value IN= 1 – 5A)
±3% of the set value or ±0.5% of the rated
value
- Operate time at definite time function
- Operate time at IDMT function
±5% or at least ±30 ms **)
*) EI = Extremely Inverse, NI = Normal Inverse, VI = Very Inverse, LTI = Long Time Inverse
MI= Moderately Inverse
**) This is the instantaneous time i.e. the minimum total operational time including the fault
detection time and operation time of the trip contacts.
Directional overcurrent stages I
dir
>>> and I
dir
>>>> (67)
Directional/non-directional
Minimum voltage for the direction solving
0.06
**)
– 300.00 s (step 0.02 s)
Transient over-reach, any τ
- Starting (rated value IN= 1 .. 5A)
±3% of the set value or ±0.5% of the rated
value
- Operate time at definite time function
**) This is the instantaneous time i.e. the minimum total operational time including the fault
detection time and operation time of the trip contacts.