VAMP 24h support phone +358 (0)20 753 3264
Short circuit distance stages Z1-Z5 (21)
0.05*) – 300.00 s (step 0.01 s)
- Starting
(when U > 1V and I > 0.5 A + UxI > 10 VA)
Typically ±5% of X (R if R > X) or 10 mΩ
- Operating time at definite time function
*) This is the instantaneous time i.e. the minimum settable total operational time including the
fault detection time and operation time of the trip contacts.
Earth-fault distance stages Z1e-Z5e (21N)
0.05*) – 300.00 s (step 0.01 s)
Start Io current setting range
0.01 - 8.00 x I
0n
0.05 … 20.0 When I
0Calc
I
0
( input X1-7 & 8)
I
0Calc
( = I
L1
+I
L2
+I
L3
)
- Starting
(when U > 1V and I > 0.5 A + UxI > 10 VA)
Typically ±5% of X (R if R > X) or 10 mΩ
- Operating time at definite time function
*) This is the instantaneous time i.e. the minimum total operational time including the fault
detection time and operation time of the trip contacts.
Distance common settings (21 and 21N)
±0.2 Ω of set value (when setting is 1.0 -5.0)
NOTE! All distance zones are using angle memory when voltage of all phase is
dropped below 0.5 V. Angle memory is active for maximym of 500 ms. So
if the tripping time of zones is more than 0.5 s, there won’t be trip.
Direction checkin of angle memory function is based on U1.