9.3.6. Synchrocheck function
DD;DL;LD;DD/DL;DD/LD;DL/LD;DD/DL/LD
±2when Δf < 0.2 Hz, else ±5
NOTE! When “sync” mode is used, Δf should be less < 0.2 Hz.
9.3.7. Second harmonic function
2. Harmonic stage (51F2)
- Setting range 2.Harmonic
0.05 – 300.00 s (step 0.01 s)
NOTE! The amplitude of second harmonic content has to be at least 2% of the
nominal of CT. If the moninal current is 5 A, the 100 Hz component needs
to exceed 100 mA.
9.3.8. Circuit-breaker failure protection
Circuit-breaker failure protection CBFP (50BF)
T1-T14 (depending the ordering code)
0.1** – 10.0 s (step 0.1 s)
**) This is the instantaneous time i.e. the minimum total operational time including the fault
detection time and operation time of the trip contacts.