EasyManua.ls Logo

VAMP 259 - Distance Protection Z; Short Circuit Distance Protection Z< (21)

VAMP 259
304 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.4 Distance protection Z<
2 Protection functions
Technical description
54
VAMP 24h support phone +358 (0)20 753 3264
VM259.EN007
2.4. Distance protection Z<
2.4.1. Short circuit distance protection Z< (21)
The distance protection function calculates the impedance Z =
U/I of the short circuit fault loops.
If impedance is inside the tripping zone (normally presented in
R-X plane), the distance function operates. In short circuit
faults there are 3 possible fault loops. The VAMP distance
protection function calculates the impedances of the fault loops
continuously and thus separate pick-up conditions are not
needed.
Figure 2.4.1-1 An example of tripping zone. Gray area is the tripping zone,
polygonal characteristics.
Figure 2.4.1-2 Short circuit fault loops and formulas to calculate the fault
impedances.
Zones and characteristics
There are 5 zones (Z1, Z2, Z3, Z4 and Z5) for short circuit
protection. These are implemented as protection stages Z1<,
Z2<, Z3<, Z4< and Z5<. Z1 extension can be implemented by
applying second setting group to cover the extension zone in
auto-reclosing.
The distance protection‘s zones implement a polygonal
characteristics as shown in Figure 2.4.1-3.

Table of Contents