2.4 Distance protection Z<
VAMP 24h support phone +358 (0)20 753 3264
Figure 2.4.1-3 The distance protection polygonal characteristics. In this
example zone 3 is in reverse direction and zone 5 is non-directional.
Parameters of the distance protection stage (21) :
Reverse/Forw
ard/
Undirectional
Common parameters for all zones
X-, R- and Load resistance settings are secondary impedances.
Primary values of settings are displayed in VAMPSET
and display.
Voltage memory
A 0.5 second cyclic buffer storing the phase-to-earth voltages is
used as voltage memory. The stored phase angle information is
used as direction reference if all the phase voltages drop below
1% during a fault.