Undervoltage stages U<, U<< and U<<< (27)
- Operating time U<
- Operating time U<< and U<<<
0.08
*)
– 300.00 s (step 0.02 s)
0.06
*)
– 300.00 s (step 0.02 s)
0.06 – 300.00 s (step 0.02 s)
Reset time for U<< and U<<<
Reset ratio (hysteresis)
Reset ratio (Block limit)
1.001 – 1.200 (0.1 20.0 %, step 0.1 %)
0.5 V or 1.03 (3 %)
±3% of set value or ±0.5 V
*) This is the total operational time including the fault detection time and operation time of the
trip contacts.
Zero sequence voltage stages U
0
> and U
0
>> (59N)
Zero sequence voltage setting range
0.3 – 300.0 s (step 0.1 s)
±2% of the set value or ±0.3% of the rated value
- Starting UoCalc (3LN mode)
9.3.4. Frequency protection
Overfrequency and underfrequency protection stages f><
and f>><< (81H/81L)
Current and voltage meas. range
Frequency stage setting range
0.10**
)
– 300.0 s (step 0.02 s)
3% of the set value or ±0.5 V
*) Suitable frequency area for low voltage blocking is 45 - 65 Hz. Low voltage blocking is
checking the maximum of line to line voltages.
**) This is the instantaneous time i.e. the minimum total operational time including the fault
detection time and operation time of the trip contacts.