3.2 Disturbance recorder
3 Supporting functions
Technical description
148
VAMP 24h support phone +358 (0)20 753 3264
VM259.EN007
Disturbance recorder parameters
Parameter
Value
Unit
Description
Note
Mode
Saturated
Overflow
Behaviour in memory full
situation:
No more recordings are
accepted
The oldest recorder will be
overwritten
Set
SR
32/cycle
16/cycle
8/cycle
1/10ms
1/20ms
1/200ms
1/1s
1/5s
1/10s
1/15s
1/30s
1/1min
Sample rate
Waveform
Waveform
Waveform
One cycle value
*)
One cycle value
**)
Average
Average
Average
Average
Average
Average
Average
Set
Time
s
Recording length
Set
PreTrig
%
Amount of recording data
before the trig moment
Set
MaxLen
s
Maximum time setting.
This value depends on
sample rate, number and
type of the selected
channels and the
configured recording
length.
Status

Run
Trig
FULL
Status of recording
Not active
Waiting a triggering
Recording
Memory is full in saturated
mode
ManTrig

Trig
Manual triggering
Set
ReadyRec
n/m
n = Available recordings
m = maximum number of
recordings
The value of 'm' depends on
sample rate, number and
type of the selected
channels and the
configured recording
length.