6.2.2 Assemble plenum rear and side panels
NOTE: Grilles can be installed on different sides of the plenum depending on discharge configuration.
Verify grill location and install according to facility-layout plans.
NOTE: Electrical connections and some piping connections are made through the plenum. Plan
accordingly.
1. Apply factory-supplied gasket/insulation tape to plenum panels, Figure 7.7 on the next page:
Onfront solid panels and onfront and rear grilled panels install the gasketing on the inner edge of the
sides, and along the top and bottom edges.
Onrear solid panels, install the gasketing onthe inner edge of the sides and along the bottom edge only.
Onside panels, install the gasketing along the bottom edge.