Document: LT0439 Vigilant MX1-Au Operator Manual
Issue 1.73 23 October 2018 Page 11-15
The Mini-Gens must be connected to the ANC3 relay output since this is
the only one with sufficient current rating and suitable supervision. This
relay can be configured for full supervision of up to three branches of
loudspeaker wiring, using the 27k ELDs provided with the MX1.
Do not use the 9k or 18k ELDs as they are not suitable for use with
100V lines.
All Mini-Gens must have their 2W supervision link fitted. If all three
branches of wiring are not used, the extra 27k ELD resistors must be
connected across the last Mini-Gen’s DC terminals.
An ISO 8201 Strobe Driver Module (PA1043) can be fitted instead of a
Mini-Gen to drive T3 synchronised strobes.
When the Alert and Evacuation tones must be separately controlled by
the MX1, one of the GP OUT terminals can be connected to the Mini-
Gen’s Alert input, as shown in the diagram. This is not default operation,
and the MX1 must be specially configured.
Optional Control of
Alert
2W link
fitted
MINI GEN
MK2
+
-
LINE
OUT
+
-
LINE
OUT
27k ELD on
100V line
Optionally link
SYNC terminals if
tones must be
synchronised
0V
SUP
NC
C
VBF+
NO
DC
IN
+
VE
- VE
SUP
+
ALERT
-
SYNC
-
Earth second
Mini-Gen to first
Mini-Gen
DC
IN
+
VE
- VE
SUP
+
ALERT
-
SYNC
-
Mount earth loom with M4 crosshead screw to
threaded hole here for earthing to gearplate
27k ELD on
spare DC
terminals
27k ELD on
100V line
2W link
fitted
MINI GEN
MK2
Use
double-insulated
ELV wiring
GP Output
MX1 CONTROLLER
ANC RELAY 3 ANC RELAY 2 ANC RELAY 1
Figure 11-11 – Mini-Gen Wiring to Anc 3