Manual VIPA System 200V Chapter 1 Basics and Assembly
HB97E - CPU - RE_21x-1Bx06 - Rev. 13/20 1-15
In the most times it is enough to take care of some elementary rules to
guarantee the EMC. Please regard the following basic rules when installing
your PLC.
Take care of a correct area-wide grounding of the inactive metal parts
when installing your components.
- Install a central connection between the ground and the protected
earth conductor system.
- Connect all inactive metal extensive and impedance-low.
- Please try not to use aluminum parts. Aluminum is easily oxidizing
and is therefore less suitable for grounding.
When cabling, take care of the correct line routing.
- Organize your cabling in line groups (high voltage, current supply,
signal and data lines).
- Always lay your high voltage lines and signal res. data lines in
separate channels or bundles.
- Route the signal and data lines as near as possible beside ground
areas (e.g. suspension bars, metal rails, tin cabinet).
Proof the correct fixing of the lead isolation.
- Data lines must be laid isolated (for details see below).
- Analog lines must be laid isolated. When transmitting signals with
small amplitudes the one sided laying of the isolation may be
favorable.
- Lay the line isolation extensively on an isolation/protected earth con-
ductor rail directly after the cabinet entry and fix the isolation with
cable clamps.
- Make sure that the isolation/protected earth conductor rail is
connected impedance-low with the cabinet.
- Use metallic or metalized plug cases for isolated data lines.
In special use cases you should appoint special EMC actions.
- Wire all inductivities with erase links, which are not addressed by the
System SLIO modules.
- For lightening cabinets you should avoid luminescent lamps.
Create a homogeneous reference potential and ground all electrical
operating supplies when possible.
- Please take care for the targeted employment of the grounding
actions. The grounding of the PLC is a protection and functionality
activity.
- Connect installation parts and cabinets with the System SLIO in star
topology with the isolation/protected earth conductor system. So you
avoid ground loops.
- If potential differences between installation parts and cabinets occur,
lay sufficiently dimensioned potential compensation lines.
Basic rules for
EMC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the VIPA CPU Series and is the answer not in the manual?

VIPA CPU Series Specifications

General IconGeneral
SeriesVIPA CPU Series
Communication PortsEthernet
Power Supply24 V DC
Operating Temperature0°C to +60°C
CertificationsCE, UL, cUL

Related product manuals