Maintenance G 150 / 180 / 240
wc_tx000868gb.fm 52
3.2 Breaking In New Machines
Run the generator at least 60–100% of continuous load for the first 100 hours.
Change engine oil and replace oil filter after the first 100 hours.
3.3 Resetting the Periodic Maintenance Timer
Background
After maintenance has been performed on the generator, it is necessary to reset
the periodic maintenance timer.
Operation
If the periodic maintenance timer is at zero, press the ENG. HRS switch UP and
hold for 10 seconds until the “TIME TO SERVICE” resets to 250 hours.
If the service time is greater than zero (maintenance was performed prior to the
timer running out) press and hold the ENG. HRS switch UP and hold for 30
seconds. This will reset the “TIME TO SERVICE” to 250 hours.