COMMISSIONING INSTRUCTIONS
TR05A140.B1107
38
Parameter 4 – CH pump mode
Access the parameters menu as described in Section 5.7.1.
Use the & buttons to adjust the parameter value:
00 = Runs when controls call for heat
01 = Runs continuously when appliance is on
Press and release the
button.
The parameter number (4) will appear on the display.
To store your changes, switch the appliance off then on again using
the ON/OFF button.
Parameter 5
Not applicable to this appliance
Parameter 6 – Short-cycling prevention (CH delay timer)
Access the parameters menu as described in Section 5.7.1.
Use the & buttons to adjust the parameter value:
00 = 0 x 5 seconds = 0 seconds (minimum)
90 = 90 x 5 seconds = 450 seconds (maximum)
Note: Factory preset to 36 = 180 seconds
Press and release the
button.
The parameter number (6) will appear on the display.
To store your changes, switch the appliance off then on again using
the ON/OFF button.
Parameter 7 – CH pump overrun timer
Access the parameters menu as described in Section 5.7.1.
Use the & buttons to adjust the parameter value:
00 = 0 x 5 seconds = 0 seconds (minimum)
90 = 90 x 5 seconds = 450 seconds (maximum)
Note: Factory preset to 36 = 180 seconds
Press and release the
button.
The parameter number (7) will appear on the display.
To store your changes, switch the appliance off then on again
using the ON/OFF button.
7
36
S
S
7
36
S
S
7
36
S
S