Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 7 – BOILER SEQUENCING TECHNOLOGY
OMM-0145_D • GF-218 • 11/2/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 113 of 213
OPTION 2 Instructions: Constant Setpoint with Modbus Wired Header Temp Sensor
On the BST Manager only:
1. Go to Main Menu → Advanced Setup → BST Cascade, set the Parameters to the Values
in each menu in the table below.
Enabled (This is available on the Manager
unit only)
Enter the designated backup unit address
Application
Configuration
Header temperature required for the cascade
The minimum unit address in the cascade
The maximum unit address in the cascade
The baud rate for the cascade.