Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 2: OPERATION
OMM-0145_D GF-218 11/2/2020 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 17 of 213
Time
Numeric Entry
Specify Auto Calibrate time of day (Calibration
Frequency = Daily).
Main Menu Calibration Input/Output Analog Inputs
Analog Name
Select
Select: Flow or Remote Analog In.
Offset
Numeric Entry
A correction value to selected input, if needed.
Current Reading
Read Only
Current reading of selected input.
Main Menu Calibration Input/Output Analog Outputs
Analog Name
Read Only
Displays the name Analog Output.
Level
Numeric Entry
Set the output’s level (0.00 to 20.00 mA)
Offset
Numeric Entry
A correction value to the analog output, if needed (-2.00 to
2.00).
Feedback
Read Only
Displays feedback from Analog Output.
2.3.2.2 Main Menu
Calibration
Subsystems
Main Menu Calibration Subsystems Air Fuel Valve
Valve Position
Manual Adjust
Set to desired Valve Position.
A/F Sensitivity
Numeric Entry
Set Air/Fuel Valve sensitivity (1% to 5%)
Main Menu Calibration Subsystems Spark Monitor
Spark Monitor
Enabled/Disabled
Enables/Disables the Spark Monitor.
Min Spark
Numeric Entry
Minimum spark. (0.00 to 0.29 amps)
Max Spark
Numeric Entry
Maximum spark. (0.30 to 2.50 amps)
2.3.2.3 Main Menu
Calibration
Combustion Summary
Main Menu Calibration Combustion Summary
Valve Position
Read Only
Displays combustion calibration valve steps.
O2
Read Only
Displays combustion calibration O2 results.
NOx
Read Only
Displays combustion calibration NOx results.
CO
Read Only
Displays combustion calibration CO results.
Flame Strength
Read Only
Displays combustion calibration flame strength.
2.3.3 Diagnostics Menu
The Diagnostics menu contains the following sections:
2.3.3.1 Main Menu
Diagnostics
Manual Run
Main Menu Diagnostics Manual Run
Manual Mode
Enable/Disable
Enables/disables running in Manual Mode.
Fire Rate
Adjust
Manual fire rate adjustment, 0 to 100%.
O2
Read Only
The percentage of O
2
in the unit’s exhaust.
Flame Strength
Read Only
The flame strength sensed in the burner, 0 to 100%.

Table of Contents

Other manuals for Watts AERCO Benchmark BMK5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Watts AERCO Benchmark BMK5000 and is the answer not in the manual?

Watts AERCO Benchmark BMK5000 Specifications

General IconGeneral
BrandWatts
ModelAERCO Benchmark BMK5000
CategoryBoiler
LanguageEnglish

Related product manuals