Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 2: OPERATION
OMM-0145_D • GF-218 • 11/2/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 17 of 213
Specify Auto Calibrate time of day (Calibration
Frequency = Daily).
Main Menu → Calibration → Input/Output → Analog Inputs
Select: Flow or Remote Analog In.
A correction value to selected input, if needed.
Current reading of selected input.
Main Menu → Calibration → Input/Output → Analog Outputs
Displays the name Analog Output.
Set the output’s level (0.00 to 20.00 mA)
A correction value to the analog output, if needed (-2.00 to
2.00).
Displays feedback from Analog Output.
2.3.2.2 Main Menu
→
Calibration
→
Subsystems
Main Menu → Calibration → Subsystems → Air Fuel Valve
Set to desired Valve Position.
Set Air/Fuel Valve sensitivity (1% to 5%)
Main Menu → Calibration → Subsystems → Spark Monitor
Enables/Disables the Spark Monitor.
Minimum spark. (0.00 to 0.29 amps)
Maximum spark. (0.30 to 2.50 amps)
2.3.2.3 Main Menu
→
Calibration
→
Combustion Summary
Main Menu → Calibration → Combustion Summary
Displays combustion calibration valve steps.
Displays combustion calibration O2 results.
Displays combustion calibration NOx results.
Displays combustion calibration CO results.
Displays combustion calibration flame strength.
2.3.3 Diagnostics Menu
The Diagnostics menu contains the following sections:
2.3.3.1 Main Menu
→
Diagnostics
→
Manual Run
Main Menu → Diagnostics → Manual Run
Enables/disables running in Manual Mode.
Manual fire rate adjustment, 0 to 100%.
The percentage of O
2
in the unit’s exhaust.
The flame strength sensed in the burner, 0 to 100%.