EasyManuals Logo

Watts AERCO Benchmark BMK5000 User Manual

Watts AERCO Benchmark BMK5000
213 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #117 background imageLoading...
Page #117 background image
Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 7 BOILER SEQUENCING TECHNOLOGY
OMM-0145_D GF-218 11/2/2020 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 117 of 213
7.3.4 Option 4 Outdoor Reset: Modbus Header Temp Sensor & Modbus Outdoor
Temp Sensor
OPTION 4 Instructions: Outdoor Reset, Modbus Header Temp Sensor & Modbus Outdoor
Temp Sensor
NOTE:
Both Header Temp Sensor and Outdoor Sensor must be wired. See the Edge [i] Controller
Manual (OMM-0141, GF-213-B) for more information.
OPTION 4 Step 1: HEADER TEMP SENSOR WIRING ANY BOILER
Using the Modbus Transmitter gives the plant the ability to use the Backup manager
feature. This allows any of the client units to become a Backup manager if the manager
unit is not communicating.
1. Connect the Modbus Transmitter terminal Pin B to the RS485+ terminal, and Pin A to the
RS485- terminal on the I/O Board of any Boiler unit, using shielded pair 18 - 22 AWG cable.
2. Connect the Header Temp Sensor (P/N 61040) to pins 2 and 3 of the Modbus Transmitter,
using shielded pair 18 - 22 AWG cable.
3. Install a jumper wire between pins 1 and 2 of the Modbus Transmitter.
NOTES:
Polarity must be observed for the RS485 connections.
Ground the shield to any SHLD terminal on the I/O Board.
The Header Temp Sensor must be installed between 2 and 10 feet (0.61 and 3.1m)
downstream of the last boiler in the plant’s supply water header.
There is no polarity to be observed. The ground for the shield is at the power supply
ground. The sensor end of the shield must be left free and ungrounded.
OPTION 4 Step 2: OUTDOOR SENSOR WIRING
1. If you have not already done so, complete step 1 of the instructions above to connect the
Modbus Transmitter to the I/O Board.
2. Connect the Outdoor Temp Sensor to Pins 5 and 6 of the Modbus Transmitter using a
shielded pair 18 - 22 AWG cable.
3. On the Modbus Transmitter, install a jumper wire between Pins 4 and 5.
MODBUS TRANSMITTER
HEADER TEMP SENSOR
I/O BOARD
MODBUS TRANSMITTER
OUTDOOR TEMP SENSOR
I/O BOARD

Table of Contents

Other manuals for Watts AERCO Benchmark BMK5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Watts AERCO Benchmark BMK5000 and is the answer not in the manual?

Watts AERCO Benchmark BMK5000 Specifications

General IconGeneral
BrandWatts
ModelAERCO Benchmark BMK5000
CategoryBoiler
LanguageEnglish

Related product manuals