Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 5 SAFETY DEVICE TESTING
OMM-0145_D GF-218 11/2/2020 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 88 of 213
Water Temperature Fault Test Instructions
5. The unit should start once the adjustable Temperature Limit switch setting is above the
actual outlet water temperature.
Figure 5-5b: Temperature Limit Switch Location BMK1500-3000 Shown
5.6 INTERLOCK TESTS
The unit is equipped with two interlock circuits called the Remote Interlock and Delayed
Interlock. Terminal connections for these circuits are located in the I/O Box (see Section 2.11.1:
I/O Board Connections in the Benchmark 750-6000 with Edge [i]: Install-Startup Manual (OMM-
0144, GF-217) and are labeled REMOTE INTL’K IN and DELAYED INTL’K IN.
These circuits can shut down the unit in the event an interlock is opened. Both interlocks are
shipped from the factory jumpered (closed). However, they may be utilized in the field as a
remote stop and start, an emergency cut-off, or to prove that a device such as a pump, gas
booster or louver is operational.
5.6.1 Remote Interlock Test
Remote Interlock Test Instructions
1. Remove the cover from the I/O Box and locate the REMOTE INTL’K IN terminals.
2. On the Controller, go to: Main Menu Diagnostics Manual Mode, then enable the
Manual Run control.
3. Set the valve position between 25% and 30% using the + (Plus) and (Minus) controls.
4. If there is a jumper across the REMOTE INTL’K IN terminals, remove one side of the
jumper. If the interlock is being controlled by an external device, either open the interlock
via the external device or disconnect one of the wires leading to the external device.
5. The unit should shut down and the Controller should display Interlock Open.
6. Once the interlock connection is reconnected, the Interlock Open message should
automatically clear and the unit should restart.
ADJUSTABLE
TEMPERATURE
LIMIT SWITCH
MANUAL
SWITCH
RESET
BUTTON
OVER
TEMPERATURE
LIMIT DIGITAL
CONTROLLER
MANUAL
TEMPERATURE
LIMIT SWITCH

Table of Contents

Other manuals for Watts AERCO Benchmark BMK5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Watts AERCO Benchmark BMK5000 and is the answer not in the manual?

Watts AERCO Benchmark BMK5000 Specifications

General IconGeneral
BrandWatts
ModelAERCO Benchmark BMK5000
CategoryBoiler
LanguageEnglish

Related product manuals