Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 3 - START SEQUENCE
OMM-0145_D GF-218 11/2/2020 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 48 of 213
3.4.9 Benchmark 6000 Air/Fuel Valve Position and Energy Input
TABLE 3-10a: BMK6000 Air/Fuel Valve Position and Energy Input
AIR/FUEL VALVE POSITION
(% OPEN)
ENERGY INPUT
(BTU/HR.)
BOILER ENERGY INPUT
(% OF FULL CAPACITY)
10%
0
0%
18% (Stop Level)
385,000 (113 kW)
6%
20%
400,000 (117 kW)
7%
30%
540,000 (158 kW)
9%
40%
770,000 (226 kW)
13%
50%
1,160,000 (340 kW)
19%
60%
1,650,000 (484 kW)
28%
70%
2,386,000 (699 kW)
40%
80%
3,515,000 (1030 kW)
59%
90%
4,650,000 (1362 kW)
78%
TABLE 3-10b: BMK6000 Gas Pressure De-Rating Chart
Applies to all models except Low Gas Pressure (LGP) models
Gas Pressure @ SSOV
in inches W.C. (kPa)
Energy Input in
BTU/hr
Oxygen
(%O
2
)
De-rating
(% Full Fire)
Inlet
Outlet
56” (13.9 kPa)
8” (1.99 kPa)
6,000,000 (1758 kW)
5.40
0%
14” (3.49 kPa)
8” (1.99 kPa)
6,000,000 (1758 kW)
5.40
0%
13” (3.23 kPa)
8” (1.99 kPa)
5,860,000 (1717 kW)
5.45
2%

Table of Contents

Other manuals for Watts AERCO Benchmark BMK5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Watts AERCO Benchmark BMK5000 and is the answer not in the manual?

Watts AERCO Benchmark BMK5000 Specifications

General IconGeneral
BrandWatts
ModelAERCO Benchmark BMK5000
CategoryBoiler
LanguageEnglish

Related product manuals