Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 3 - START SEQUENCE
OMM-0145_D GF-218 11/2/2020 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 39 of 213
3.3 START/STOP LEVELS
The start and stop levels are the Air/Fuel Valve positions (% open) that start and stop the unit,
based on load. These levels are Factory preset as follows:
TABLE 3-1a: Start/Stop Levels NATURAL GAS
BMK
750
BMK
1000
BMK
1500
BMK
2000
BMK
2500
BMK
3000
BMK
4000
BMK
5000N
BMK
4000 &
5000N
DF
BMK
5000
BMK
6000
Start
Level:
22%
22%
20%
24%
24%
20%
27%
24%
24%
24%
24%
Stop
Level:
18%
18%
16%
18%
16%
14%
23%
18%
18%
18%
18%
Ignition
Position
35%
35%
29%
29%
29%
29%
45%
40%
35%
35%
50%
TABLE 3-1b: Start/Stop Levels PROPANE GAS
BMK
750
BMK
1000
BMK
1500
BMK
2000
BMK
2500
BMK
3000
BMK
4000
BMK
5000N
BMK
5000
BMK
6000
Start
Level:
22%
22%
20%
24%
26%
22%
24%
24%
24%
24%
Stop
Level:
18%
18%
16%
18%
18%
14%
18%
18%
18%
18%
Ignition
Position
35%
35%
29%
29%
29%
29%
35%
35%
35%
50%
Normally, these settings do not require adjustment.
Note that the energy input of the boiler is not linearly related to the Air/Fuel Valve position.

Table of Contents

Other manuals for Watts AERCO Benchmark BMK5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Watts AERCO Benchmark BMK5000 and is the answer not in the manual?

Watts AERCO Benchmark BMK5000 Specifications

General IconGeneral
BrandWatts
ModelAERCO Benchmark BMK5000
CategoryBoiler
LanguageEnglish

Related product manuals