Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 5 SAFETY DEVICE TESTING
OMM-0145_D GF-218 11/2/2020 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 89 of 213
5.6.2 Delayed Interlock Test
Delayed Interlock Test Instructions
1. Remove the cover from the I/O Box and locate the DELAYED INTL’K IN terminals.
2. On the Controller, go to: Main Menu Diagnostics Manual Mode, then enable the
Manual Run control.
3. Set the valve position between 25% and 30% using the + (Plus) and (Minus) controls.
4. If there is a jumper across the DELAYED INTL’K IN terminals, remove one side of the
jumper. If the interlock is connected to a proving switch of an external device, disconnect
one of the wires leading to the proving switch.
5. The unit should shut down and display a Delayed Interlock Open fault message. The
FAULT LED should be flashing.
6. Reconnect the wire or jumper removed in step 5 to restore the interlock.
7. Press the CLEAR button to reset the fault
8. The unit should start.