EasyManua.ls Logo

Watts AERCO Benchmark BMK5000 - Safety Device Testing; Burner Inspection

Watts AERCO Benchmark BMK5000
213 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 8 MAINTENANCE
OMM-0145_D GF-218 11/2/2020 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 137 of 213
8.5 SAFETY DEVICE TESTING
Systematic and thorough tests of the operating and safety devices should be performed to
ensure that they are operating as designed. Certain code requirements, such as ASME CSD-1,
require that these tests be performed on a scheduled basis. Test schedules must conform to
local jurisdictions. The results of the tests should be recorded in a log book.
See Section 5: Safety Device Testing in this guide for a description and instructions for
performing these tests.
8.6 BURNER INSPECTION
The burner assembly should be inspected every 24 months to ensure that all components are
intact and functioning as designed. This requires the replacement of one or two burner gaskets
(depending on BMK model), and blower and gas train O-Rings, which are included in all 24
Month Maintenance Kits. If the burner is not fully intact, it must be replaced as soon as
possible.
The burner assembly is located at the top of the unit's heat exchanger. The burner assembly
may be hot. Therefore, allow the unit to cool sufficiently before removing the burner assembly.
Burner inspection parts are included all 24 Month Maintenance Kits. Instructions are in the
Technical Instruction Documents (TIDs) included with the kits:
Figure 8-5a: Burner Assembly Exploded View BMK750/1000
AIR/FUEL VALVE
BURNER GASKET
(P/N 81143)
FLAME DETECTOR
O
2
SENSOR
BLOWER GASKET
(P/N 81064)
BURNER
BLOWER
BURNER PLATE
PIPE FLANGE GASKET
(P/N 81155)
GAS TRAIN
CONNECTS HERE

Table of Contents

Other manuals for Watts AERCO Benchmark BMK5000

Related product manuals