OPTION 3 Step 3 –DAISY CHAIN WIRING BETWEEN BOILERS
1. Connect the boilers in a daisy chain, as shown below.
OPTION 3 Step 4 –CONFIGURATION
On All Boilers:
1. Go to: Main Menu → Advanced Setup → BST Cascade → Cascade Configuration and set
the Unit Mode parameter to BST Client.
2. Go to: Main Menu → Advanced Setup → BST Cascade → Cascade Communication and
set the Unit Address parameter to the communication address of the unit.
Continued on next page