Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 7 BOILER SEQUENCING TECHNOLOGY
OMM-0145_D GF-218 11/2/2020 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 130 of 213
OPTION 8 Instructions: Remote Setpoint, Modbus Header Temp Sensor & Modbus Setpoint
Drive
Using the Modbus Transmitter gives the plant the ability to use the Backup manager
feature. This allows any of the client units to become a Backup manager if the manager
unit is not communicating.
On the BST Manager only:
1. Go to Main Menu Advanced Setup BST Cascade, set the Parameters to the Values
in each menu in the table below.
Menu/Screen Name
Parameters
Values
Cascade
Configuration
Unit Mode
BST Manager
Hdr Temp Sensor
Network
Sensor Comm Address
240
Hdr Temp Point
14
Application
Configuration
Application
Space Heating
SH Operating Mode
Rmt Setpt Netwrk
Cascade Comm
Min address
The minimum unit address in the cascade
Max address
The maximum unit address in the cascade
Cascade Baud Rate
The baud rate for the cascade.