Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 7 – BOILER SEQUENCING TECHNOLOGY
OMM-0145_D • GF-218 • 11/2/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 130 of 213
OPTION 8 Instructions: Remote Setpoint, Modbus Header Temp Sensor & Modbus Setpoint
Drive
Using the Modbus Transmitter gives the plant the ability to use the Backup manager
feature. This allows any of the client units to become a Backup manager if the manager
unit is not communicating.
On the BST Manager only:
1. Go to Main Menu → Advanced Setup → BST Cascade, set the Parameters to the Values
in each menu in the table below.
Application
Configuration
The minimum unit address in the cascade
The maximum unit address in the cascade
The baud rate for the cascade.