Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 2: OPERATION
OMM-0145_D • GF-218 • 11/2/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 29 of 213
Defines a Shutoff delay, during which time the unit remains
at minimum fire rate after the unit has sequenced to
shutoff. It is activated only when Off Delay Threshold is
reached (0 to 9999 secs). (Slow Shutdown = Enabled).
The Fire rate that activates the Off Delay function
(40 to 100 %). (Slow Shutdown = Enabled).
Specifies the number of degrees above setpoint that the
outlet temperature can rise without triggering a unit shut
down (0 to 25°F).
The temperature offset from setpoint before a unit may
come online. (0°F to 25°F). This can reduce excessive
cycling in AUTO mode. When above 0, the unit will not turn
on again until Valve Position In reaches the Start Level
value AND the outlet temperature goes below Demand
Offset; the unit will fire at the ignition valve position or
below for 1 minute. If this entry equals 0, the unit will turn
on when the Valve Position In = Start Level.