EasyManua.ls Logo

West Control Solutions Pro-EC44 - Page 148

West Control Solutions Pro-EC44
272 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014 Page 142
Plug-in Module Slot 3 Parameters
Parameter Name & Register Address
Integer Int +1 Float Access Values & Descriptions
Plug-in Module 3 Type Value Module Fitted In Slot 3
Dec 2192 18576 37152
RO
0 None Fitted
Hex 0890 4890 9120
1 Single Relay
2 Single SSR Driver
3
Error (invalid module for this slot)
8 Triac
9 Dual Relay
10 Dual SSR Driver
11 24VDC Transmitter PSU
255
Error (unrecognised module)
Output 3 or 3A Status Value Output 3 or 3A Status
Dec 2194 18578 37156
RO
0 Inactive
Hex 0892 4892 9124
1 Active
Output 3B Status Value Output 3B Status
Dec 2195 18579 37158
RO
0 Inactive
Hex 0893 4893 9126
1 Active
Digital Output 3 Latch Enable Value Output 3 or 3A Enable / Disable Latching
Dec 2197 18581 37162
RW
0 Disabled
Hex 0895 4895 912A
1 Enabled
Digital Output 3 Clear Latch Value Output 3 or 3A Latch Clear
Dec 2198 18582 37164
RW
0 Do Nothing
Hex 0896 4896 912C
1 Clear Latch
Digital Output 3 Latch State Value Output 3 or 3A Latch State
Dec 2199 18583 37166
RO
0 Unlatched
Hex 0897 4897 912E
1 Latched
Digital Output 3B Latch Enable Value Output 3B Enable / Disable Latching
Dec 2200 18584 37168
RW
0 Disabled
Hex 0898 4898 9130
1 Enabled
Digital Output 3B Clear Latch Value Output 3B Latch Clear
Dec 2201 18585 37170
RW
0 Do Nothing
Hex 0899 4899 9132
1 Clear Latch
Digital Output 3B Latch State Value Output 3B Latch State
Dec 2202 18586 37172
RO
0 Unlatched
Hex 089A 489A 9134
1 Latched
Output 3 Function Value Output 3 or 3A Function
Dec 10103 26487 52974
RW
0 Disabled
Hex 2777 6777 CEEE
1 Loop 1 Primary Output Power
2 Loop 1 Secondary Output Power
3 Loop 1 VMD Open
4 Loop 1 VMD Close
5 Loop 2 Primary Output Power
6 Loop 2 Secondary Output Power
7 Loop 2 VMD Open
8 Loop 2 VMD Close
9 OR Alarm Event Direct

Table of Contents