Fault finding and diagnosis
83
Greenstar 2000 – 6 721 820 552 (2021/02)
Table 36 Indicators and fault displays
2964 B Flow rate in heat exchanger too low Check the flow through the appliance and that the system is filled.
Check for air locks in the system and purge if required.
Check the heat exchanger sensor (primary thermistor) and the plug connected to the
temperature sensor.
Check the resistance of the temperature sensor and replace if required.
Check the continuity of the harness and replace if required.
2965 B Flow temperature too high Check the flow through the appliance and the system is filled.
Check for the air locks in the system and purge if required.
Check the isolation valves.
2966 B Flow temperature rise in heat exchanger too
rapid
Check the flow through the appliance and the system is filled.
Check for the air locks in the system and purge if required.
Check the isolation valves.
Check the pump is operating freely and check the voltage to the pump.
2967 B Flow/heat exchanger temperature sensor
differential too great
Check the flow through the appliance and the system is filled.
Check for air locks in the system and purge if required.
Check the isolation valves.
Check the pump is operating freely and check the voltage to the pump.
Check the heat exchanger sensor and the flow sensor are making contact with the
pipework.
Check the heat exchanger sensor and the resistance of the temperature sensor and
replace if required.
Check the continuity of harness and replace if required.
2972 Mains voltage too low Check the mains voltage on the appliance (L and N).
2973 System fault boiler electronics / basic
controller
Perform factory reset.
Check and replace control unit.
2974 Internal fault Restart the appliance and check if fault remains.
Check and replace control unit.
3071 Comfort + II RF Check the configuration (address setting). The selected setting requires a remote
control.
Check the EMS connection cable for the remote control for damage. The BUS voltage on
the remote control must be between 12 and 15 V DC.
The remote control is defective.
Fault
code
Fault
category
Description Remedy

Table of Contents

Other manuals for Worcester GR2300iW C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Worcester GR2300iW C and is the answer not in the manual?

Worcester GR2300iW C Specifications

General IconGeneral
BrandWorcester
ModelGR2300iW C
CategoryBoiler
LanguageEnglish

Related product manuals