Current Sharing (6000 Watt only)
Overview
Release 3.0 175
SCPI
Select whether the unit will operate as a master or slave unit:
SOURCE:COMBine:CSHare:MODE [MASTer | SLAVe | OFF]
To query the total output current of all current sharing units, use the SCPI command:
MEAS:CURR? SUM
The current share subregister (CSHare) will show whether the master or slave is
operating.
STAT:OPER:CSH:COND?
See Table 4.14, “Current SHare Sub-Register,” on page 148 for a description of the
bits in this register.
Setup
Current
Sharing
Network
To set up multiple supplies for current share operation, follow these steps:
1. Configure each supply with a unique multichannel address. (See “Multichannel
Operation (6000 Watt only)” on page 113.)
Configure one supply to operate as the master. Configure others to operate as
slaves.
2. Power down the units. Connect the CAN ports of all paralleled units as you
would for multichannel operation
3. Make load connections. It is recommended to keep load cables the same length
if possible. See Figure 5.1.
4. Power up the master, then all slaves.
5. Set the voltage on the master, then enable the output.