Specifications and Characteristics
Electrical Specifications—Summary
Release 3.0 233
Table E.6Drift Specifications for 12000 Watt units (10V to 60V Models)
Models 10–1200 20–600 30–400 40–300 60–200
Drift (30 minutes):
1
Voltage (0.04% of Vmax)
Current (0.6% of Imax)
1. Maximum drift over 30 minutes with constant line, load, and temperature, after power on.
4mV
7200 mA
8mV
3600 mA
12 mV
2400 mA
16 mV
1800 mA
24 mV
1200 mA
Drift (8 hours):
2
Voltage (0.02% of Vmax)
Current (0.05% of Imax)
2. Maximum drift over 8 hours with constant line, load, and temperature, after 30 minute warm-up.
2mV
600 mA
4mV
300 mA
6mV
200 mA
8mV
150 mA
12 mV
100 mA
Temperature Coefficient:
3
Voltage (0.04% of Vmax/°C)
Current (0.06% of Imax/°C)
3. Change in output per °C change in ambient temperature, with constant line and load.
4mV
720 mA
8mV
360 mA
12 mV
240 mA
16 mV
180 mA
24 mV
120 mA