P266 MOTOR NOM.VOLT.
230 V
Actual Value Output Freq.
Left fct. Up fct. Down fct. Right fct.
Possible settings are:
HVL Possible setting (V) Default setting (V)
2.015 ÷ 2.040 208–240 230
3.015 ÷ 3.110 208–240 230
4.015 ÷ 4.220 380–460 400
P267 MOTOR NOM.FRQ.
Sets the motor nominal frequency, as reported in the motor nameplate
P267 MOTOR NOM.FRQ.
50.0 Hz
Actual Value Output Freq.
Left fct. Up fct. Down fct. Right fct.
P268 MOTOR NOM.CURR.
Sets the motor nominal current, as reported in the motor nameplate, according to
the chosen motor connection
the output voltage of the HYDROVAR
P268 MOTOR NOM.CURR.
7.5 A
Actual Value Output Freq.
Left fct. Up fct. Down fct. Right fct.
P269 MOTOR NOM.SPEED
Sets the motor nominal speed, as reported in the motor nameplate
P269 MOTOR NOM.SPEED
3000 rpm
Actual Value Output Freq.
Left fct. Up fct. Down fct. Right fct.
P270 MOTOR POLES
This parameter (possible setting 2 or 4) sets the number of motor poles (display showing,
for example, the following information)
8 Programming
64 HVL 2.015-4.220 Installation, Operation, and Maintenance Manual

Table of Contents

Other manuals for Xylem hydrovar

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xylem hydrovar and is the answer not in the manual?

Xylem hydrovar Specifications

General IconGeneral
Frequency50/60 Hz
Control typeVariable speed drive
Protection classIP55
Communication protocolsModbus
Relative Humidity5% - 95% (non-condensing)
AltitudeUp to 1000 m without derating
Input voltage200-690 V AC
Storage Temperature-25°C to +70°C (-13°F to 158°F)

Related product manuals