P1203 PROTOCOL
P1203 PROTOCOL
Modbus RTU
Actual Value Output Freq.
Left fct. Up fct. Down fct. Right fct.
Sets the desired communication protocol.
Possible settings are:
Disabled
Modbus RTU
Modbus ASCII
BACNet MS/TP
P1205 ADDRESS
P1205 ADDRESS
1
Actual Value Output Freq.
Left fct. Up fct. Down fct. Right fct.
Sets the desired address (possible setting 1 - 247) for the user interface.
P1210 BAUD RATE
P1210 BAUD RATE
9600
Actual Value Output Freq.
Left fct. Up fct. Down fct. Right fct.
Set the BAUD RATE for the user interface.
Possible settings are:
1200
2400
4800
9600
14400
19200
38400
57600
76800
115200
8 Programming
90 HVL 2.015-4.220 Installation, Operation, and Maintenance Manual