P1215 FORMAT
P1215 FORMAT
8, N, 1
Actual Value Output Freq.
Left fct. Up fct. Down fct. Right fct.
Set the data FORMAT for the communication port, depending on the value of P1203
PROTOCOL
Possible settings are:
8, E, 1
8, O, 1
8, N, 2
8, N, 1
7, E, 1
7, O, 1
7, N, 2
7, N, 1
P1220 PUMP ADDR.
P1220 PUMP ADDR.
1
Actual Value Output Freq.
Left fct. Up fct. Down fct. Right fct.
Selects an address for each inverter.
P1221 BACNET DEV. ID
P1221 BACNET DEV.ID
84001
Actual Value Output Freq.
Left fct. Up fct. Down fct. Right fct.
Sets Bacnet Device Object ID
P1225 SSID NUMBER
P1225 SSID NUMBER
01234567
Actual Value Output Freq.
Left fct. Up fct. Down fct. Right fct.
This parameter shows the identification number of the Wi-Fi network generated when the
wireless module is assembled into HYDROVAR.
In particular, the network name will be: "hydrovar__P1225__", where P1225 is the value of
this parameter, expressed as an 8 character word.
8 Programming
HVL 2.015-4.220 Installation, Operation, and Maintenance Manual 91