EasyManua.ls Logo

YASKAWA CIPR-GA50CB001

YASKAWA CIPR-GA50CB001
794 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter List
11
11.4 A: Initialization Parameters
YASKAWA SIEPC71061753C GA500 Technical Manual 359
11.4 A: Initialization Parameters
A1: Initialization
No.
(Hex.)
Name Description
Default
(Range)
Ref.
A1-00
(0100)
RUN
Language Selection
Sets the language for the LCD keypad.
Note:
When you use A1-03 [Initialize Parameters] to initialize the drive, the drive will
not reset this parameter.
0 : English
1 : Japanese
2 : German
3 : French
4 : Italian
5 : Spanish
6 : Portuguese
7 : Chinese
8 : Czech
9 : Russian
10 : Turkish
11 : Polish
12 : Greek
0
(0 - 12)
483
A1-01
(0101)
RUN
Access Level Selection
Sets user access to parameters. The access level controls which parameters the keypad
will display, and which parameters the user can set.
0 : Operation Only
1 : User Parameters
2 : Advanced Level
3 : Expert Level
2
(0 - 3)
483
A1-02
(0102)
Control Method
Selection
Sets the control method for the drive application and the motor.
0 : V/f Control
2 : Open Loop Vector
5 : PM Open Loop Vector
6 : PM Advanced Open Loop Vector
8 : EZ Vector Control
0
(0, 2, 5, 6, 8)
484
A1-03
(0103)
Initialize Parameters
Sets parameters to default values.
0 : No Initialization
1110 : User Initialization
2220 : 2-Wire Initialization
3330 : 3-Wire Initialization
0
(0 - 3330)
485
A1-04
(0104)
Password
Entry point for the password set in A1-05 [Password Setting]. The user can view the
settings of parameters that are locked without entering the password. Enter the correct
password in this parameter to change parameter settings.
0000
(0000 - 9999)
486
A1-05
(0105)
Password Setting
Set the password to lock parameters and prevent changes to parameter settings. Enter
the correct password in A1-04 [Password] to unlock parameters and accept changes.
0000
(0000 - 9999)
486
A1-06
(0127)
Application Preset
Sets the drive to operate in selected application conditions.
0 : General-purpose
1 : Water Supply Pump 2
2 : Conveyor
3 : Exhaust Fan
4 : HVAC Fan
5 : Air Compressor
6 : Crane (Hoist)
7 : Crane (Traveling)
8 : Conveyor 2
0
(0 - 8)
487
A1-07
(0128)
DriveWorksEZ Function
Selection
Sets the drive to operate with DriveWorksEZ.
0 : DWEZ Disabled
1 : DWEZ Enabled
2 : Enabled/Disabled wDigital Input
0
(0 - 2)
499
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents