EasyManua.ls Logo

YASKAWA CIPR-GA50CB001

YASKAWA CIPR-GA50CB001
794 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
12
12.6 E: Motor Parameters
YASKAWA SIEPC71061753C GA500 Technical Manual 593
E3-01: Motor 2 Control Mode Selection
No.
(Hex.)
Name Description
Default
(Range)
E3-01
(0319)
Motor 2 Control Mode
Selection
Sets the control method for motor 2.
0
(0, 2)
Note:
When you change this setting, the drive will set all parameters that are dependent on E3-01 to their default settings.
Parameter L1-01 [Motor Overload (oL1) Protection] sets the protection operation of oL1 [Motor Overload] the same as Motor 1.
When you use parameter A1-03 [Initialize Parameters] to initialize the drive, this parameter is not reset.
0 : V/f Control
2 : Open Loop Vector
E3-04: Motor 2 Maximum Output Frequency
No.
(Hex.)
Name Description
Default
(Range)
E3-04
(031A)
Motor 2 Maximum Output
Frequency
Set the maximum output frequency for the motor 2 V/f pattern.
Determined by E3-01
(40.0 - 590.0 Hz)
E3-05: Motor 2 Maximum Output Voltage
No.
(Hex.)
Name Description
Default
(Range)
E3-05
(031B)
Motor 2 Maximum Output
Voltage
Sets the maximum output voltage for the motor 2 V/f pattern.
Determined by E3-01
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
E3-06: Motor 2 Base Frequency
No.
(Hex.)
Name Description
Default
(Range)
E3-06
(031C)
Motor 2 Base Frequency
Sets the base frequency for the motor 2 V/f pattern.
Determined by E3-01
(0.0 - E3-04)
E3-07: Motor 2 Mid Point A Frequency
No.
(Hex.)
Name Description
Default
(Range)
E3-07
(031D)
Motor 2 Mid Point A
Frequency
Sets a middle output frequency for the motor 2 V/f pattern.
Determined by E3-01
(0.0 - E3-04)
E3-08: Motor 2 Mid Point A Voltage
No.
(Hex.)
Name Description
Default
(Range)
E3-08
(031E)
Motor 2 Mid Point A
Voltage
Sets a middle output voltage for the motor 2 V/f pattern.
Determined by E3-01
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
E3-09: Motor 2 Minimum Output Frequency
No.
(Hex.)
Name Description
Default
(Range)
E3-09
(031F)
Motor 2 Minimum Output
Frequency
Sets the minimum output frequency for the motor 2 V/f pattern.
Determined by E3-01
(0.0 - E3-04)
E3-10: Motor 2 Minimum Output Voltage
No.
(Hex.)
Name Description
Default
(Range)
E3-10
(0320)
Motor 2 Minimum Output
Voltage
Sets the minimum output voltage for the motor 2 V/f pattern.
Determined by E3-01
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA CIPR-GA50CB001

Related product manuals