1.21 Defaults by Drive Model and Duty Rating ND/HD
140 YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
No.
*1
Name Unit Default
- Drive Model - 4007 4009 4012 4018
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 95 96 97 99
E2-11
(E4-11, E5-
02)
Motor Rated
Power
kW 2.2 3.0 3.0 3.7 4.0 5.5 5.5 7.5
L3-24
Motor Accel
Time @ Rated
Torque
s 0.145 0.145 0.145 0.154 0.154 0.168 0.168 0.175
L8-02
Overheat
Alarm Level
°C 90 90 115 115 110 110 120 120
L8-09
Output Ground
Fault
Detection
- 0 0 0 0 0 0 0 0
n1-03
Hunting
Prevention
Time Constant
ms 10 10 10 10 10 10 10 10
n3-02
HSB Current
Limit Level
% 150 120 150 120 150 120 150 120
n5-02
Motor Inertia
Acceleration
Time
s 0.145 0.145 0.145 0.154 0.154 0.168 0.168 0.175
*1 Parameters within parentheses are for motor 2.
No.
*1
Name Unit Default
- Drive Model - 4023 4031 4038 4044
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 9A
REV:A: 9C
REV:B: 19C
*2
REV:A: 9D
REV:B: 19D
*2
9E
E2-11
(E4-11, E5-
02)
Motor Rated
Power
kW 7.5 11 11 15 15 18.5 18.5 22
b3-04
V/f Gain
during Speed
Search
% 100 100 100 100 100 100 100 100
b3-06
Speed
Estimation
Current Level
1
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-08
Speed
Estimation
ACR P Gain
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-26
Direction
Determination
Level
- 1000 1000 1000 1000 1000 1000 1000 1000
b8-03
Energy Saving
Filter Time
s 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b8-04
Energy Saving
Coefficient
Value
- 145.38 140.88 140.88 126.26 126.26 115.74 115.74 103.58
C6-02
Carrier
Frequency
Selection
- 3 7 3 7 3 7 3 7
E2-01
(E4-01)
Motor Rated
Current (FLA)
A 13.3 19.9 19.9 26.5 26.5 32.9 32.9 38.6
E2-02
(E4-02)
Motor Rated
Slip
Hz 1.3 1.7 1.7 1.6 1.6 1.67 1.67 1.7