Parameter List
3
3.21 Defaults by Drive Model and Duty Rating ND/HD
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting 301
No.
*1
Name Unit Default
- Drive Model - T103 T140 T168 T208
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 01A3 01A4 01A5 01A6
E2-11
(E4-11, E5-
02)
Motor Rated
Power
HP
(kW)
60
(45)
75
(55)
75
(55)
100
(75)
100
(75)
125
(90)
125
(90)
150
(110)
E2-10
(E4-10)
Motor Iron
Loss
W 1125 1260 1260 1600 1600 1760 1760 2150
E5-01
PM Motor
Code Selection
- 1244 1244 1245 1245 1246 1246 1247 1247
L2-02
Power Loss
Ride Through
Time
s 2 2 2 2 2 2 2 2
L2-03
Minimum
Baseblock
Time
s 1.2 1.2 1.2 1.3 1.3 1.5 1.5 1.7
L2-04
Powerloss V/f
Recovery
Ramp Time
s 0.6 1 1 1 1 1 1 1
L2-05
Undervoltage
Detection Lvl
(Uv1)
- 380 380 380 380 380 380 380 380
L3-24
Motor Accel
Time @ Rated
Torque
s 0.387 0.317 0.317 0.533 0.533 0.592 0.592 0.646
L8-02
Overheat
Alarm Level
°C 126 120 120 120 110 110 105 105
L8-09
Output Ground
Fault
Detection
- 1 1 1 1 1 1 1 1
L8-38
Carrier
Frequency
Reduction
- 2 2 2 2 2 2 2 2
n1-01
Hunting
Prevention
Selection
- 2 2 2 2 2 2 2 2
n1-03
Hunting
Prevention
Time Constant
ms 10 10 30 30 30 30 30 30
n1-16
Hunting
Prevention
High Fc Gain
- 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
n5-02
Motor Inertia
Acceleration
Time
s 0.387 0.317 0.317 0.533 0.533 0.592 0.592 0.646
*1 Parameters within parentheses are for motor 2.