When P9-12 is set to 2, the output frequency must also fall below the level set in P9-13.
No. Name Setting Range Default
P9-14 Remove Delta Level 0.0 to 6000.0 0.0 PSI
n
P9-15: Remove Delay Time
Sets the delay time before the lead drive is removed from the system.
No. Name Setting Range Default
P9-15 Remove Delay Time 0 to 3600 s 10 s
n
P9-16: Stabilization Time
Sets the time used to stabilize the system when a pump is staged or de-staged. Lead-lag control and pump protection is
suspended during this time.
No. Name Setting Range Default
P9-16 Stabilization Time 0 to 3600 s 3 s
n
P9-17: Setpoint Modifier
The system setpoint is incremented with the P9-17 value depending on the number of pumps running.
Pump 1: Setpoint
Pump X: Setpoint + ((X-1) (P9-17))
No. Name Setting Range Default
P9-17 Setpoint Modifier -999.9 to 999.9 0.0 PSI
n
P9-18: High Feedback Quick De-Stage
Sets the feedback level to trigger a quick de-stage as a percentage of parameter P1-09.
No. Name Setting Range Default
P9-18 High Feedback Quick De-Stage 0.0 to 100.0% 97.0%
The quick de-stage ignores parameters P9-12 to P9-15 and only uses an internal 2-second delay. A setting of 0.0 disables the
High Feedback De-stage feature.
n
P9-19: Alternation Unit
Selects the units for parameter P9-03, Alternation Time.
No. Name Setting Range Default
P9-19 Alternation Unit 0, 1 0
Setting 0: Hours
Setting 1: Minutes
n
P9-20: Allow Network Run
No. Name Setting Range Default
P9-20 Allow Network Run 0 to 3 0
Setting 0: Always
Allows the drive to respond to all network Run commands (first drive, staging, alternation).
Setting 1: First/Alternation
The drive is limited to being either the first drive or for alternation.
Setting 2: First only
The drive can only be a first drive.
5.11 P: Pump