LED Display LCD Display Error Name
The following simultaneous contradictory
settings:
H3-02 or H3-06 = B (PID Feedback) while
H6-01
(Pulse Train Input) = 1 (PID Feedback)
H3-02 or H3-06 = C (PID Target Value)
while H6-01 = 2
(pulse train input sets the PID target value)
Disable one of the PID selections.
LED Display LCD Display Error Name
ope09
oPE09
PID Control Selection Fault
PID control function selection is incorrect. Requires that PID control is enabled (b5-01 = 1).
Cause Possible Solutions
b5-01 is set to 1 or 2, enabling PID control,
but the lower limit for the frequency
reference (d2-02) is not set to 0 while reverse
output is enabled
(b5-11 = 1).
Correct the parameter settings.
LED Display LCD Display Error Name
ope10
oPE10
V/f Data Setting Error
One of the following setting errors has occurred:
E1-09 E1-07 < E1-06 E1-11 E1-04
Cause Possible Solutions
V/f pattern setting error. Correct the settings for E1-04, E1-06, E1-07, E1-09, and E1-11.
LED Display LCD Display Error Name
ope11
oPE11
Carrier Frequency Setting Error
Correct the setting for the carrier frequency.
Cause Possible Solutions
The following simultaneous contradictory
settings have occurred: C6-05 > 6 and C6-04
> C6-03 (carrier frequency lower limit is
greater than the upper limit).
If C6-05 6, the drive operates at C6-03.
Correct the parameter settings.
The upper and lower limits between C6-02
and C6-05 are contradictory.
LED Display LCD Display Error Name
ope33
oPE33
Net
Incompatible
Parameter selection is incompatible with the selected network P9-99
Cause Possible Solutions
When P1-01 = 3 (MEMOBUS Networking)
and P9-99 = 0 (A-Version 30034), one of the
following parameters has been set:
P9-01 = 2 (Stop History)
P9-05 = 3 (Follow Lead Speed)
Confirm parameter settings for P1-01, P9-01, P9-99, and P9-05.