No.
(Addr.
Hex)
Name LCD Display Description
Analog
Output Level
Unit
U4-10
(005C)
kWh, Lower 4 Digits kWh Lower 4 dig
Monitors the drive output power usage (or consumption). The
value is shown as a 9-digit number displayed across two monitor
parameters, U4-10 and U4-11.
Example:
12345678.9 kWh is displayed as:
U4-10: 678.9 kWh
U4-11: 12345 MWh
No signal output
available
1 kWh
U4-11
(005D)
kWh, Upper 5 Digits kWh Upper 5 dig
No signal output
available
1 MWh
U4-13
(07CF)
Peak Hold Current Current PeakHold
Displays the highest current value that occurred during run.
No signal output
available
0.01 A
<3> <4>
<5>
U4-14
(07D0)
Peak Hold Output
Frequency
Freq@ I PeakHold
Displays the output frequency when the current value shown in
U4-13 occurred.
No signal output
available
0.01 Hz
U4-16
(07D8)
Motor Overload
Estimate (oL1)
Motor OL1 Level
Shows the value of the motor overload detection accumulator.
100% is equal to the oL1 detection level.
10 V: 100% 0.1%
U4-18
(07DA)
Frequency Reference
Source Selection
Reference Source
Displays the source for the frequency reference as XY-nn.
X: indicates which reference is used:
1 = Reference 1 (b1-01)
2 = Reference 2 (b1-15)
Y-nn: indicates the reference source
0-01 = Digital operator
1-00 = Analog
1-01 = Analog (terminal A1)
1-02 = Analog (terminal A2)
1-03 = Analog (terminal A3)
2-02 to 17 = Multi-step speed (d1-02 to 17)
3-01 = MEMOBUS/Modbus communications
4-01 = Communication option card
5-01 = Pulse input
9-01 = Up/Down Command
No signal output
available
U4-19
(07DB)
Frequency Reference
from MEMOBUS/
Modbus Comm.
MEMOBUS Freq Ref
Displays the frequency reference provided by MEMOBUS/
Modbus (decimal).
No signal output
available
0.01%
U4-20
(07DC)
Option Frequency
Reference
Option Freq Ref
Displays the frequency reference input by an option card
(decimal).
No signal output
available
U4-21
(07DD)
Run Command Source
Selection
Run Cmd Source
Displays the source for the Run command as XY-nn.
X: Indicates which Run source is used:
1 = Reference 1 (b1-02)
Y: Input power supply data
0 = Digital operator
1 = External terminals
3 = MEMOBUS/Modbus communications
4 = Communication option card
nn: Run command limit status data
00: No limit status.
01: Run command was left on when stopped in the PRG mode
02: Run command was left on when switching from LOCAL to
REMOTE operation
03: Waiting for soft charge bypass contactor after power up (Uv
or Uv1 flashes after 10 s)
04: Waiting for “Run command prohibited” time period to end
05: Fast Stop (digital input, digital operator)
06: b1-17 (Run command given at power-up)
07: During baseblock while coast to stop with timer
08: Frequency reference is below minimal reference during
baseblock
09: Waiting for Enter command
10: Run command was switched on while copying parameters
12: Clock is being set for RTC
No signal output
available
U4-22
(07DE)
MEMOBUS/Modbus
Communications
Reference
MEMOBUS Ref Reg
Displays the drive control data set by MEMOBUS/Modbus
communications register no. 0001H as a four-digit hexadecimal
number.
No signal output
available
U4-23
(07DF)
Communication Option
Card Reference
Option Ref Reg
Displays drive control data set by an option card as a four-digit
hexadecimal number.
No signal output
available
<1> The MEMOBUS/Modbus communications data is in 10 h units. If data in 1 h units are also required, refer to register number 0099H.
<2> The MEMOBUS/Modbus communications data is in 10 h units. If data in 1 h units are also required, refer to register number 009BH.
<3> Display is in the following units:
B.16 U: Monitors
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
375
B
Parameter List