Register No. Contents
00CDH
bit 0 NETSCAN Wait for Master
bit 1 Pump Cycling Pump Over Cycle
bit 2 Low Feedback Low FB Sensed
bit 3 High Feedback High FB Sensed
bit 5 Freq. Ref < Pump Min P1-06
bit 6 Freq. Ref < Thrust (P4-12)
bit 7 Low City Pressure
bit 8 Anti-Jam Active
bit B Feedback Loss Wire Break
bit D R-DNE-Sx : Remote Drv Dis
bit E Low Suction Pressure
bit F Low Water in Tank
00CEH
bit 2 Time Not Set (TIM)
bit 3 Battery Low (bAT)
bit 4 Time Deviation Error (TdE)
bit 5 Setpoint Not Met (NMS)
bit 6 Emergency Override FWD (EoF)
bit 7 Emergency Override REV (Eor)
bit 8 bit 8 - Feedback Loss Go To B5-13
00D0H
CPF Contents 1
bit 0 to 1 Reserved
bit 2 A/D Conversion Error (CPF02)
bit 3 PWM Data Fault (CPF03)
bit 4 to 5 Reserved
bit 6 Drive specification mismatch during Terminal Board or Control Board replacement (CPF06)
bit 7 Terminal Board Communications Fault (CPF07)
bit 8 EEPROM Serial Communications Fault (CPF08)
bit 9 to A Reserved
bit B RAM Fault (CPF11)
bit C FLASH Memory Fault (CPF12)
bit D Watchdog Circuit Exception (CPF13)
bit E Control Circuit Fault (CPF14)
bit F Reserved
00D1H
CPF Contents 2
bit 0 Clock Fault (CPF16)
bit 1 Timing Fault (CPF17)
bit 2 Control Circuit Fault (CPF18)
bit 3 Control Circuit Fault (CPF19)
bit 4 Hardware fault at power up (CPF20)
bit 5 Hardware fault at communication start up (CPF21)
bit 6 A/D Conversion Fault (CPF22)
bit 7 PWM Feedback Fault (CPF23)
bit 8 Drive capacity signal fault (CPF24)
bit 9 Terminal board is not properly connected (CPF25)
bit A to F Reserved
C.10 MEMOBUS/Modbus Data Table
410
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual