Related Parameters, Faults, and Alarms
No. Parameter Name Setting Values
A1-01 Access Level Selection
Default: 2
Range: 0 to 3
A1-03 Initialize Parameters
Default: 0
Range: 0 to 5550; 6008 to 6011; 7770
b1-02 Run Command Selection 1
Default: 0
Range: 0 to 3
E2-01 Motor Rated Current
Default:
Min.: 10% of drive rated current
Max.: 200% of drive rated current
E2-04 Number of Motor Poles
Default: 2
Min.: 2
Max.: 48
P1-03 Feedback Device Scaling
Default: 145.0 PSI
Min.: 0.1
Max.: 6000.0
P1-04 Start / Draw Down Level
Default: 0.0
Min.: -999.9
Max.: 999.9
P1-06 Minimum Pump Speed
Default: 40.0 Hz
Min.: 0.0
Max.: [E1-04]
P1-11 High Feedback Level
Default: 0.0 PSI
Min.: 0.0
Max.: 6000.0
P2-02 Sleep Level
Default: 0.0 Hz
Min.: 0.0
Max.: 6000.0
P4-10 AUTO Mode Operator Run Power Down Storage
Default: 0
Range: 0, 1
P5-02 HAND Speed Reference 1
Default: 40.0 Hz
Min.: 0
Max.: [E1-04]
P5-04 HAND Key Function Selection
Default: 1
Range: 0, 1
Q1-01 PID Controller Setpoint 1
Default: 0.0
Min.: 0.0
Max.: 6000.0
Q2-01 Minimum Geothermal Temperature Input
Default: 0.0 °F
Min.: -110.0
Max.: 275.0
Q2-02 Maximum Geothermal Temperature Input
Default: 120.0 °F
Min.: -100.0
Max.: 275.0
Q2-03 Minimum Geothermal Speed
Default: 40.0 Hz
Min.: 0.0
Max.: 400.0
Q2-04 Maximum Geothermal Speed
Default: 60.0 Hz
Min.: 0.0
Max.: 400.0
Q2-05 Low Temperature to Run at Maximum Geothermal Speed
Default: 55.0 °F
Min.: -110.0
Max.: 275.0
Q2-06 Low Temperature to Run at Minimum Geothermal Speed
Default: 65.0 °F
Min.: -110.0
Max.: 275.0
4.5 iQpump Presets and Functions
124