No.
(Addr.
Hex)
Name LCD Display Description Values Page
P4-13
(0D06)
Thrust Bearing
Deceleration Time
Thrust Dec Time
Sets the amount of time it takes to bring the drive from the Thrust
Frequency set in P4-12 to stop when Thrust Mode is active.
When the Run command is removed while the drive is operating
in Thrust Mode above the Thrust Frequency, the time set in this
parameter is used when the frequency reference is at or below
the thrust frequency.
Default: 5.0 s
Min.: 0.0
Max.: 600.0
P4-17
(0D0A)
Utility Start Delay Utility Delay
Sets the amount of time that the drive will delay starting if a Run
command is present at power-up.
When P1-01, Pump Mode, is set to 3 (MEMOBUS network),
the drive is unavailable to the network (Pump Off Network)
when the function is active.
Setting this parameter to 0.0 disables the function.
Default: 0.2 min
Min.: 0.0
Max.: 1000.0
168
P4-21
(0D0E)
Low City Input Select
Low City In Sel
0: Normally Open
1: Normally Closed
Selects the type of pressure switch connected to the “Low City
Press” digital input (H1-0o = 73).
0: Normally open (closed indicates the Low City Pressure
condition)
1: Normally closed (open indicates the Low City Pressure
condition)
Default: 1
Range: 0, 1
P4-22
(0D0F)
Low City On-Delay
Time
Low City On Dly
Sets the amount of time a Low City Pressure condition needs to
be present before the drive will stop.
Default: 10 s
Min.: 1
Max.: 1000
P4-23
(0D10)
Low City Off-Delay
Time
Low City Off Dly
Sets the amount of time a Low City Pressure condition needs to
be absent before the drive will restart.
Default: 5 s
Min.: 0
Max.: 1000
P4-24
(0D11)
Low City Alarm Text
Low City Alarm Txt
0: Low Cty Pressure
1: Low Suction Pres
2: Low Watr in Tank
Selects the alarm message that will be displayed when a Low
City Pressure condition is detected.
0: Low city pressure
1: Low suction pressure
2: Low water in tank
Default: 0
Range: 0 to 2
P4-25
(0D12)
Remote Drive Disable
Selection
Rem Drv Dis Sel
0: Normally Open
1: Normally Closed
Selects the type of pressure switch connected to the “Remote
Drive Disable” digital input (H1-0o = 95).
0: Normally open (closed indicates the Remote Drive Disable
condition)
1: Normally closed (open indicates the Remote Drive Disable
condition)
Default: 1
Range: 0, 1
P4-26
(0D13)
Remote Drive Disable
On-Delay
Drv Dis On-Delay
Sets the amount of time a Remote Drive Disable condition must
be present before the drive will stop.
Default: 0 s
Min.: 0
Max.: 1000
P4-27
(0D14)
Remote Drive Disable
Off-Delay
Drv Dis OffDelay
Sets the amount of time a Remote Drive Disable condition must
be absent before the drive will run.
Default: 0 s
Min.: 0
Max.: 1000
P4-31
(0D18)
Lube Pump Delay
Timer
Lube Pump Time
Sets the amount of time to delay the drive output and to energize
the Lube Pump digital output (H2-oo = 8B) before the drive
is allowed to run.
Setting this parameter to 0.0 disables the function.
Default: 0.0 s
Min.: 0.0
Max.: 300.0
<1> Unit is determined by P1-02, Ssytem Units, setting.
<2> Unit text is set by P1-18, Prime Loss Detection Method.
u
P5: Pump HAND Mode
No.
(Addr.
Hex)
Name LCD Display Description Values Page
P5-01
(0D2C)
HAND Mode Ref
Source
Hand Mode Ref.
0: Analog Input
1: Hand Ref 1 (OPR)
Sets the HAND Mode reference.
0: Analog input A1 (0-10 V)
1: P5-02 (HAND reference)
Default: 1
Range: 0, 1
P5-02
(0D2D)
HAND Reference 1 HAND Reference 1
Sets the frequency reference used when HAND Mode is active
and P5-01 is set to 1.
Default: 40.0 Hz
Min.: 0
Max.: [E1-04]
169
B.11 P: Pump Parameters
308