4.4 Pump Application Presets
The following sections list the parameters affected by the different Application Presets.
Note: Setting A1-03 to 6011 (VTC Pressure Control) changes the Quick Start and Pre-set parameters (tables below) and also changes HAND
Mode so that it is no longer lower-limited by the minimum pump frequency or the thrust frequency. Also, the default for P1-06 when in
RPM mode is 1800 RPM instead of 2400 RPM.
u
Parameters Set Depending on A1-03 Setting
The following table shows the parameters that are set depending on the A1-03 initialization:
A1-03 = 6008
(A1-06 = 8)
Pressure Control
A1-03 = 6009
(A1-06 = 9)
Pump Down Level
A1-03 = 6010
(A1-06 = 10)
Geothermal Mode
A1-03 = 6011
(A1-06 = 11)
VTC Pressure Ctl
A1-03 = 7770
(A1-06 = 1)
General Purpose
Parameter Value Parameter Value Parameter Value Parameter Value Parameter Value
b5-09 1 b1-01 5 b5-03 5.0 b1-01 1
b5-39 2 b5-01 0 C1-01 15.0 sec b1-02 1
P1-02 6 H3-10 21 C1-02 15.0 sec b5-01 0
P2-01 2 o1-08 180 E2-04 4 C1-01 25.0 sec
P2-23 0.00% L5-01 0 C1-02 25.0 sec
P1-03 100.0 PSI H1-06 4
P1-06 35.0 Hz H1-07 F
P2-03 15sec H2-01 0
P2-23 0.00% H2-02 A
P3-50 35.0 Hz H3-10 2
P3-60 35.0 Hz L5-01 0
P3-70 35.0 Hz L5-04 180.0 sec
P4-12 0.0 Hz o1-06 0
P5-02 6.0 Hz P1-05 0 sec
Q5-03 40.0 PSI P1-06 0.0 Hz
Q5-06 50.0 PSI P4-12 0.0 Hz
Q5-09 20.0 PSI P4-17 0.0 min
Q5-10 5.0 min P5-02 0.0 Hz
Q5-11 2
Q5-16 1.00
Q5-17 3.0 sec
H2-01 80H
H2-02 81H
H2-03 82H
4.4 Pump Application Presets
118