YASKAWA iQpump1000 - S3: Secondary PI (PI2) Control

YASKAWA iQpump1000
356 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
No.
(Addr.
Hex)
Name LCD Display Description Values Page
S2-15
(3214)
Sequence Timer 3
Reference Source
Tmr 3 Ref Source
0: Operator (d1-01)
1: Operator (d1-02)
2: Operator (d1-03)
3: Operator (d1-04)
4: Terminals
5: Serial com
6: Option PCB
7: Pulse Input
8: Set by b1-01
Selects the frequency reference source used for running the
drive when sequence timer 3 is active (only applicable when
S2-14 is set to 1 or 2).
0: Operator (d1-01)
1: Operator (d1-02)
2: Operator (d1-03)
3: Operator (d1-04)
4: Terminals
5: Serial communication
6: Option card
7: Pulse input
8: Set by b1-01
Default: 8
Range: 0 to 8
S2-16
(3215)
Sequence Timer 4 Start
Time
Tmr 4 Start Time
Sets the start time for timer 4. The value must be set less than
or equal to S2-17.
Default: 00:00
Min.: 00:00
Max.: 24:00
<1>
S2-17
(3216)
Sequence Timer 4 Stop
Time
Tmr 4 Stop Time
Sets the stop time for timer 4. The value must be set greater than
or equal to S2-16.
Default: 00:00
Min.: 00:00
Max.: 24:00
<1>
S2-18
(3217)
Sequence Timer 4 Day
Selection
Tmr 4 Day Sel
0: Timer disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
4: Monday
5: Tuesday
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Sets the days for which sequence timer 4 is active.
0: Timer disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
4: Monday
5: Tuesday
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Default: 0
Range: 0 to 10
S2-19
(3218)
Sequence Timer 4
Selection
Tmr 4 Seq Sel
0: Digital out only
1: Run
2: Run - PI Disable
Sets the action that occurs when sequence timer 4 is active.
0: Digital output only
1: Run
2: Run - PI disable
Default: 0
Range: 0 to 2
S2-20
(3219)
Sequence Timer 4
Reference Source
Tmr 4 Ref Source
0: Operator (d1-01)
1: Operator (d1-02)
2: Operator (d1-03)
3: Operator (d1-04)
4: Terminals
5: Serial com
6: Option PCB
7: Pulse Input
8: Set by b1-01
Selects the frequency reference source used for running the
drive when sequence timer 4 is active (only applicable when
S2-19 is set to 1 or 2).
0: Operator (d1-01)
1: Operator (d1-02)
2: Operator (d1-03)
3: Operator (d1-04)
4: Terminals
5: Serial communication
6: Option card
7: Pulse input
8: Set by b1-01
Default: 8
Range: 0 to 8
<1> Setting the sequence timer start time to a higher value than the sequence timer stop time disables that sequence timer.
u
S3: Secondary PI (PI2) Control
No.
(Addr.
Hex)
Name LCD Display Description Values Page
S3-01
(321A)
Secondary PI Enable
Selection
PI2 Enable Sel
0: Disabled
1: Always
2: Drive running
3: Motor running
Determines when the secondary PI controller is enabled.
0: Disabled
1: Always
2: Drive running
3: Motor running
Note: Setting 3 does not run the motor at zero speed,
baseblock, or in DC injection.
Default: 0
Range: 0 to 3
S3-02
(321B)
Secondary PI User
Display
PI2 UsrDspMaxVal
Sets the scale value of 100% PI input.
Default: 10000
Min.: 0
Max.: 60000
B.13 S: Special Application
322
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide