No.
(Addr.
Hex)
Name LCD Display Description
Analog
Output Level
Unit
U1-83
(0B9E)
Flow Rate Flow Rate
Displays the flow rate based on the pulse input frequency or the
analog voltage (flow rate input) and parameters P6-01 and
P6-04.
A 2-second first order filter will be applied to this monitor.
Full scale: P6-01
setting
dep. on
P6-04
U1-84
(0B9F)
Accumulation Level -
Millions
Volume * 1000000
Displays the recorded volume from the flow meter (pulse input
or analog voltage).
Total volume is calculated as follows:
Total Volume = (U1-84 * 1000000) + (U1-85 * 1000) + U1-86
+ U1-87
No signal output
available
dep. on
P6-16
U1-85
(0BA0)
Accumulation Level -
Thousands
Volume * 1000
U1-86
(0BA1)
Accumulation Level -
Ones
Volume * 1
U1-87
(0BA2)
Accumulation Level -
Decimal
Volume * 0.0001
U1-90
(0BA5)
Pump Setpoint Pump Setpoint
Displays the PID Setpoint. No signal output
available
dep. on
P1-02
U1-91
(0BA6)
Pump Feedback Pump Feedback
Displays the PID Feedback. No signal output
available
dep. on
P1-02
U1-92
(0BA7)
Pump Status Pump Status
Displays Pump Running Status.
U1
-
92=
00000000
Drive
Pump 2
Pump 3
Pump 4
Pump 5
Pump 6
Not used
Not used
1
1
1
1
1
1
0
0
No signal output
available
–
U1-93
(0BA8)
Total Setpoint
Compensation
Total SP Comp.
Displays the total absolute Setpoint Compensation. No signal output
available
dep. on
P1-02
U1-94
(0BA9)
Motor Speed Motor Speed
Displays the absolute value of the output frequency (U1-02)
converted to RPM.
No signal output
available
1 RPM
U1-97
(0BAC)
Water Level Water Level
Displays the amount of water above the water level sensor. Full scale:
10 V = Q4-02
0.1 ft.
U1-98
(0BAD)
Suction Pressure Suction Pressure
Displays the amount of suction pressure. Full scale:
10 V = Q5-02
0.1 PSI
or ”Hg
U1-99
(0BAE)
Anti-No-Flow Timer ANF Timer
The Anti-No-Flow reduces the output frequency when this
value reaches the P2-24 setting.
No signal output
available
0.1 s
<1> The number of decimal places in the parameter value depends on the drive model and the ND selection. This value has two decimal places (0.01
A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if the maximum applicable
motor capacity is higher than 11 kW.
<2> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.
<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<4> The display resolution depends on the ND selection. This value has two decimal places (0.01 kW) if the drive is set for a maximum applicable
motor capacity up to and including 11 kW, and one decimal place (0.1 kW) if the maximum applicable motor capacity is higher than 11 kW.
u
U2: Fault Trace
No.
(Addr.
Hex)
Name LCD Display Description
Analog
Output Level
Unit
U2-01
(0080)
Current Fault Current Fault
Displays the current fault. No signal output
available
–
U2-02
(0081)
Previous Fault Last Fault
Displays the previous fault. No signal output
available
–
U2-03
(0082)
Frequency Reference at
Previous Fault
Frequency Ref
Displays the frequency reference at the previous fault. No signal output
available
0.01 Hz
B.15 U: Monitors
328