Three-Phase 400 V Class Drive Models 4A0208 to 4A0675
Table A.6 Power Ratings Continued (Three-Phase 400 V Class)
Item Specification
Drive Models 4A0208 4A0250 4A0296 4A0362 4A0414 4A0515 4A0675
Maximum Applicable Motor Capacity
(HP)
<1>
ND Rating 150 200 250 300 350 400-450 500-550
Input
Input Current (A)
<2>
ND Rating 207 248 300 346 410 465 657
Rated Voltage
Rated Frequency
Three-phase: 380 to 480 Vac 50/60 Hz/510 to 680 Vdc
<3>
Allowable Voltage Fluctuation -15 to 10%
Allowable Frequency Fluctuation ±5%
Input Power (kVA) ND Rating 189 227 274 316 375 425 601
Output
Rated Output Capacity
(kVA)
<4>
ND Rating
<5>
159 191 226 276 316 392 514
Rated Output Current (A)
ND Rating
<5>
208 250 296 362 414 515 675
Overload Tolerance
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
User-adjustable between 1 and 10 kHz
<5>
User-adjustable between 1 and 5
kHz
<5>
Maximum Output Voltage (V) Three-phase: 380 to 480 V (proportional to input voltage)
Maximum Output Frequency (Hz) 400 Hz (user-adjustable)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring conditions,
and power supply impedance.
<3> DC is not available for UL/CE standards.
<4> Rated motor capacity is calculated with a rated output voltage of 440 V.
<5> Carrier frequency default setting is Swing PWM 1 (C6-02 = 7). C6-02 settings 1, 7, 8, 9, and A do not require current derating. All other settings
raise the carrier frequency and require current derating.
A.1 Power Ratings