No. Parameter Name Setting Values
P4-08 Pre-Charge Loss of Prime Level 2
Default: 0.0 A
Min.: 0.0
Max.: 1000.0
H1 Multi-Function Digital Input Settings
H1-oo
Setting
Function Description
8C Disable Pre-Charge Closed: Pre-Charge disabled.
H2 Multi-Function Digital Output Settings
H2-oo
Setting
Function Description
A4 Pre-Charge Closed: Drive is in Pre-Charge mode.
R un
C omm an d
P re-C ha rg e
Sing le speed C o m plete via t im er
Pre-cha rge
Active
M essage &
D igital Ou tpu t
(H 2-0x = A4)
Ou tpu t
F requen cy
P 4-03
Pre-cha rge T im e
P4-02 Pre-cha rge F r equen cy
P4-01 Pre-cha rge leve l = 0 .0 AND P4-07 Pr e -cha rge T im e 2 = 0 .0 m in
PID N OT
disab led
Figure 4.14 Pre-Charge Single Speed Complete via Timer
R un
C omm an d
P re-C ha rg e
D ua l speed C o m plete via t im er
Pre-cha rge
Active
M essage &
D igital Ou tpu t
(H 2-0x = A4)
Ou tpu t
F requen cy
P 4-03
Pre-cha rge T im e
P4-02 Pre-cha rge F r equen cy
P4-01 Pre-cha rge level = 0.0
P4-06 Pre -cha rge F r equen cy 2
P4-07
Pre-cha rge T im e 2
PID N OT
disab led
Figure 4.15 Pre-Charge Dual Speed Complete via Timer