Setting 0: Fault
Setting 1: Alarm
Setting 2: Digital out only
n
P2-01: Sleep Level Type
Selects which data source the drive will use to determine if it should activate the sleep function. This parameter is application-
dependent and should be set in conjunction with the type of system data is available. Choose the data type that best represents
a low-activity condition for the system.
Note: Set this parameter prior to changing other parameters related to the Sleep Function, as internal scaling is based on P2-01.
No. Parameter Name Setting Range Default
P2-01 Sleep Level Type 0 to 4 0
Setting 0: Output frequency
Setting 1: Output current
Setting 2: Feedback
Setting 3: Output speed (RPM)
Setting 4: Flow meter (requires flow meter)
n
P2-02: Sleep Level
Sets the level at which the drive will enter sleep mode. The drive will enter sleep mode when the monitored data falls below
the P2-02 setting for the time set in P2-03.
No. Parameter Name Setting Range Default
P2-02 Sleep Level 0.0 to 6000.0 0.0 Hz
n
P2-03: Sleep Delay Time
Sets the delay time after which the drive will enter sleep mode. The drive will enter sleep mode when the monitored data falls
below the P2-02 setting for the time set in P2-03.
No. Parameter Name Setting Range Default
P2-03 Sleep Delay Time 0 to 3600 0 s
n
P3-00: Number of Lag Pumps
Sets the number of lag pumps in the system. When using Contactor Multiplexing for the control lag pumps, first set P1-01 to
1. Then select the number of lag pumps to be controlled in P3-00. Set the corresponding multi-function digital outputs for lag
pumps (H2-oo = 80-82 and F5-oo = 83-84). The methods used to determine lag pump staging and de-staging order are
selected in P1-30 and P1-31.
No. Parameter Name Setting Range Default
P3-00 Number of Lag Pumps 1 to 5 1
n
P3-50: Pump 2 Frequency Shutdown Level
Sets the level at which the first lag pump (2nd pump in the system) will shut down or de-stage. This parameter is effective
when the P3-01 is set to 0 or 2 (pump staging is based on output frequency). When the output frequency falls below the P3-50
leel for the time set in P3-09, the pump will be de-staged.
No. Parameter Name Setting Range Default
P3-50 Pump 2 Frequency Shutdown Level 0.0 to 400.0 40.0 Hz
n
P3-60: Pump 3 Frequency Shutdown Level
Sets the level at which the second lag pump (3rd pump in the system) will shut down or de-stage. This parameter is effective
when the P3-01 is set to 0 or 2 (pump staging is based on output frequency). When the output frequency falls below the P3-50
leel for the time set in P3-09, the pump will be de-staged.
No. Parameter Name Setting Range Default
P3-60 Pump 3 Frequency Shutdown Level 0.0 to 400.0 40.0 Hz
4.6 Basic iQpump Setup and Application Preset Parameters
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
167