H1 Multi-Function Digital Input Selections
H1-oo
Setting
Function LCD Display Description Page
1B Program lockout Program Lockout
Open: Parameters cannot be edited (except for U1-01 if the reference source is
assigned to the digital operator).
Closed: Parameters can be edited and saved.
–
1E Reference sample hold Ref Sample Hold
Closed: Samples the analog frequency reference and operates the drive at that
speed.
–
20 to 2F External pump fault
Ext Pump Fault
20: NO/Always Det,
Ramp to Stop
21: NC/Always Det,
Ramp to Stop
22: NO/During RUN,
Ramp to Stop
23: N.C., During run,
ramp to stop
24: NO/ Always Det,
Coast to Stop
25: NC/Always Det,
Coast to Stop
26: NO/During RUN,
Coast to Stop
27: NC/During RUN,
Coast to Stop
28: NO/Always Det,
Fast-Stop
29: NC/Always Det,
Fast-Stop
2A: NO/During RUN,
Fast-Stop
2B: NC/During RUN,
Fast- Stop
2C: NO/Always Det,
Alarm Only
2D: NC/Always Det,
Alarm Only
2E: NO/ During RUN,
Alarm Only
2F: NC/During RUN,
Alarm Only
20: N.O., Always detected, ramp to stop
21: N.C., Always detected, ramp to stop
22: N.O., During run, ramp to stop
23: N.C., During run, ramp to stop
24: N.O., Always detected, coast to stop
25: N.C., Always detected, coast to stop
26: N.O., During run, coast to stop
27: N.C., During run, coast to stop
28: N.O., Always detected, Fast Stop
29: N.C., Always detected, Fast Stop
2A: N.O., During run, Fast Stop
2B: N.C., During run, Fast Stop
2C: N.O., Always detected, alarm only (continue running)
2D: N.C., Always detected, alarm only (continue running)
2E: N.O., During run, alarm only (continue running)
2F: N.C., During run, alarm only (continue running)
–
30 PID integral reset PID Intgrl Reset Closed: Resets the PID control integral value. –
31 PID integral hold PID Intgrl Hold
Open: Performs integral operation.
Closed: Maintains the current PID control integral value.
–
32
Multi-Step Speed
Reference 4
Multi-Step Ref 4
Used in combination with input terminals set to Multi-Step Speed Reference 1, 2,
and 3. Use parameters d1-09 to d1-16 to set reference values.
–
34 PID soft starter cancel PID SFS Cancel
Open: PID soft starter is enabled.
Closed: Disables the PID soft starter b5-17.
–
35 PID input level selection PID Input Invert Closed: Inverts the PID input signal. –
40
Forward run command
(2-Wire sequence)
FwdRun 2Wire Seq
Open: Stop
Closed: Forward run
Note: Cannot be set together with settings 42 or 43.
–
41
Reverse run command
(2-Wire sequence)
RevRun 2WireSeq
Open: Stop
Closed: Reverse run
Note: Cannot be set together with settings 42 or 43.
–
42
Run command
(2-Wire sequence 2)
Run/Stp 2WireSeq
Open: Stop
Closed: Run
Note: Cannot be set together with settings 40 or 41.
–
43
FWD/REV command
(2-Wire sequence 2)
FWD/REV 2WireSeq
Open: Forward
Closed: Reverse
Note: Determines motor direction, but does not issue a Run command.
Cannot be set together with settings 40 or 41.
–
47 Node setup CanOpenNID Setup Closed: Node setup for SI-S3 enabled. –
51 Sequence Timer Disable SeqTimer Disable
Closed: Drive ignores sequence timers and runs normally (based on b1-02/b1-16
source).
–
B.7 H Parameters: Multi-Function Terminals