3 Power Connections
3.1 Electrical Connections
RM2-755/1255SL
Positioner
3 Power Connections
3.1 Electrical Connections
3.1.1 Grounding
Follow the local regulations and electrical installation standards for
grounding. The recommended grounding wire size is 10 gauge (5.5 mm
2
)
or more.
Fig. 3-1: Grounding Method
WARNING
Ground resistance must be 100Ω or less.
Failure to observe this warning may result in fire or electric shock.
Before wiring, make sure to turn OFF the primary power supply, and
put up a warning sign. (ex. DO NOT TURN ON THE POWER.)
Failure to observe this warning may result in fire or electric shock.
Wiring must be performed by authorized or certified personnel.
Failure to observe this caution may result in fire or electric shock.
NOTICE
Never use this line sharing with other ground lines or grounding
electrodes for other electric power, motor power, welding devices,
etc.
Where metal ducts, metallic conduits, or distributing racks are used
for cable laying, ground in accordance with Electric Equipment
Technical Standards.
A
5.5 mm
2
or more
Bolt M8 (for grounding)
(Delivered with M3XSL Positioner)
Enlarged View A
44 of 145

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA RM2-755/1255SL and is the answer not in the manual?

YASKAWA RM2-755/1255SL Specifications

General IconGeneral
BrandYASKAWA
ModelRM2-755/1255SL
CategoryValve Positioners
LanguageEnglish

Related product manuals