5-20
Carrier Frequency: C6
* 1. The factory setting depends on the capacity of the Inverter.
* 2. The setting range depends on the capacity of the Inverter.
* 3. This constant can be monitored or set only when C6-02 is set to F.
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
C6-02
Carrier frequency
selection
Selects the carrier frequency.
Select F to enable detailed settings
using constants C6-03 to C6-05.
0 to F
6
*1
No Q 224H
4-5
4-11
6-2
C6-03
Carrier frequency
upper limit
Sets the carrier frequency upper limit
and lower limit in kHz units.
The carrier frequency gain is set as fol-
lows:
K is a coefficient that depends on the setting
of C6-03.
C6-03 ≥ 10.0 kHz: K = 3
10.0 kHz > C6-03 ≥ 5.0 kHz: K = 2
5.0 kHz > C6-03: K = 1
2.0 to
15.0
*2 *3
15.0
kHz
*1
No A 225H 6-2
C6-04
Carrier frequency
lower limit
0.4 to
15.0
*2 *3
15.0
kHz
*1
No A 226H 6-2
C6-05
Carrier frequency
proportional gain
00 to
99
*3
00 No A 227H 6-2
Carrier frequency
Output frequency x (C6-05) x K
(Max. output frequency)
Output
frequency