EasyManua.ls Logo

YASKAWA Varispeed E7 - Option Constants: F

YASKAWA Varispeed E7
290 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User Constant Tables
5-25
Option Constants: F
Communications Option Cards: F6
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
F6-01
Operation selec-
tion after commu-
nications error
Set the stopping method for com-
munications errors.
0: Deceleration to stop using the
deceleration time in C1-02
1: Coast to stop
2: Emergency stop using the
deceleration time in C1-09
3: Continue operation
0 to 3 1 No A 3A2H
F6-02
Input level of
external error
from Communica-
tions Option Card
0: Always detect
1: Detect during operation
0 or 1 0 No A 3A3H
F6-03
Stopping method
for external error
from Communica-
tions Option Card
0: Deceleration to stop using the
deceleration time in C1-02
1: Coast to stop
2: Emergency stop using the
deceleration time in C1-09
3: Continue operation
0 to 3 1 No A 3A4H
F6-05
Current monitor
unit selection
Sets the unit of current monitor
0: Ampere
1: 100%/8192
0 or 1 1 No A 3A6H
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Other manuals for YASKAWA Varispeed E7

Related product manuals